HVAC and air handler checklist

Monthly, quarterly, annual, and before-heating-season checks for rooftop units, split systems, and air handlers.

Monthly

TaskRequiredPhoto required
Before starting
Switch the unit off. Lock out and tag the main disconnect and any remote disconnects, and verify zero voltage with a meter. Discharge capacitors, and wait out any variable-frequency drive's discharge time.Yes
Rooftop units: work near the roof edge only with fall protection in place.Yes
Unit running
Observe the unit running, and note any unusual noise, vibration, or change in how it runs.Yes
Check that the controls respond to calls for fan, cooling, and heating, with no override left active.Yes
Cooling season: a certified technician checks suction and discharge pressure, superheat, and subcooling against the manufacturer's charging chart, with the unit running.YesYes
Check piping and coils for oil stains or other signs of a refrigerant leak.Yes
Check that the condensate overflow switch float moves freely.Yes
Filters
Check filters for loading. Replace or clean any that are dirty or above the manufacturer's maximum pressure drop.YesYes
Check filter fit, frame, and gaskets for gaps or bypass around the media.Yes
Where fitted: clean the permanent filters or screens in the outdoor-air hoods.
Fan and drive
Belt-drive units: check belt tension and wear, and sheave alignment and wear. Replace frayed or worn belts, as matched sets on multi-belt drives.Yes
Check the fan wheel and housing for dirt, damage, and rubbing. Turn the wheel by hand and clean it.Yes
Rooftop and split condensing units: in the cooling season, turn the condenser fans by hand. Check that they move freely and that their mounting hardware is tight.Yes
Check motor bearings, and lubricate them per the motor manufacturer.Yes
Check that motor mounts and brackets are tight.
Coils, drain pan, and condensate
Inspect the drain pan for standing water, sludge, rust, and biological growth. Clean and sanitize it. Do not walk on the drain pan.YesYes
Check that the condensate drain line and trap flow freely. Prime the P-trap.Yes
Dampers and outdoor air
Stroke the outdoor-air, return, and exhaust dampers fully open to fully closed. Check that linkages and actuators move freely, and that the outdoor-air dampers close tight.Yes
Inspect the outdoor-air intake, louvers, and bird screen for blockage, debris, nests, and any new contaminant source nearby.Yes
Electrical and controls
With power isolated, check the control panel and heat-section box for dirt, loose terminals, and damaged wire insulation. Tighten and repair as needed.Yes
Check contactors for pitting or burning. Replace them; do not clean the contacts.Yes
Cooling season: where a sight glass or gauge is fitted, check the compressor oil level.
Casing and insulation
Check access panels, doors, gaskets, and the curb. Confirm that all fasteners are in place, that gaskets seal, and that there are no air or water leaks.Yes
Inspect internal insulation and damp areas for biological growth. Clean or disinfect them.Yes
Check the casing for corrosion. Remove it and repaint bare metal where found.
Closing
Refit all access panels and every retaining screw. Remove locks and tags, restore power, and confirm the unit starts and runs in each mode.Yes
Report any defect found, and raise a follow-up work request.Yes

Quarterly

TaskRequiredPhoto required
Before starting
Switch the unit off. Lock out and tag the main disconnect and any remote disconnects, and verify zero voltage with a meter. Discharge capacitors, and wait out any variable-frequency drive's discharge time.Yes
Rooftop units: work near the roof edge only with fall protection in place.Yes
Fan and drive
Check fan shaft bearings for wear, and lubricate them per the manufacturer. Do not over-grease; some bearings are lubricated for life.Yes
Coils, drain pan, and condensate
Inspect the evaporator coil for dirt, bent fins, leaks, and biological growth. Comb the fins and clean the coil if dirty.YesYes
Where fitted: clean the moisture eliminator.
Electrical and controls
Where fitted: check that UV lamps are lit and clean.
Where fitted: check the humidifier for scale, leaks, and wetting downstream.
Closing
Refit all access panels and every retaining screw. Remove locks and tags, restore power, and confirm the unit starts and runs in each mode.Yes
Report any defect found, and raise a follow-up work request.Yes

Annual

TaskRequiredPhoto required
Before starting
Switch the unit off. Lock out and tag the main disconnect and any remote disconnects, and verify zero voltage with a meter. Discharge capacitors, and wait out any variable-frequency drive's discharge time.Yes
Rooftop units: work near the roof edge only with fall protection in place.Yes
Filters
Where fitted: check that the filter pressure gauge and its tubing are intact.
Fan and drive
Check flexible duct connections for cracks or leaks.
Coils, drain pan, and condensate
Rooftop and condensing units: inspect and clean the condenser coil, more often where the unit is in a dirty location. Clean microchannel coils with water or air only.YesYes
Check the cooling coil for moisture carryover beyond the drain pan.
Where fitted: clean the condensate pump, tank, float, and line.
Electrical and controls
Where fitted: check that the duct or return-air smoke detector's test record is current.Yes
Casing and insulation
Inspect exposed duct and pipe insulation and the vapor barrier.
Closing
Refit all access panels and every retaining screw. Remove locks and tags, restore power, and confirm the unit starts and runs in each mode.Yes
Report any defect found, and raise a follow-up work request.Yes

Before the heating season

TaskRequiredPhoto required
Before starting
Switch the unit off. Lock out and tag the main disconnect and any remote disconnects, and verify zero voltage with a meter. Discharge capacitors, and wait out any variable-frequency drive's discharge time.Yes
Rooftop units: work near the roof edge only with fall protection in place.Yes
Coils, drain pan, and condensate
Where fitted: for hot-water or steam coils, check for leaks. Before freezing weather, confirm each coil is drained or protected against freezing.
Gas heat
Gas-fired units: inspect the heat exchanger for corrosion, cracks, or holes.YesYes
Gas-fired units: check and clean the burners, flue, and combustion air blower. Look for dirt, blockage, and nests.Yes
Gas-fired units: run a heat test. Confirm that ignition lights reliably and that the unit heats. Check combustion against the manufacturer's specification.YesYes
Closing
Refit all access panels and every retaining screw. Remove locks and tags, restore power, and confirm the unit starts and runs in each mode.Yes
Report any defect found, and raise a follow-up work request.Yes

Where the unit maker's manual gives a different interval or step, follow the manual.